Call us for help!

+(27) 11 674 4011

Our Location

Fauchard Building, Cnr. Jan Smuts Drive & Jan Hofmeyer Avenue Florida Park, 1709

30 kW | 102 000 Btu

EE1650
Item No.: 9005401001 Category: Schlagwort

The delivery system is equipped with two floats that operate separately. The working float switches the pump on and off, depending on the fill level (with a run-on time). The alarm float toggles the normally-closed contact potential-free. An integrated non-return valve prevents the backflow of condensate into the container.

EE1650_Web_Header
  • pump unit
Noise level 30 dB (A) DIN EN 3745
~ < 24 dB(A) DIN EN 3744
For air conditioners up to 30 kW
Drive Solenoid pump
Mains voltage & frequenxy 230V, 50/60Hz
Power consumption Operation 40W, Standby 1 W
Max. flow rate 32 l/h
Max. delivery height 15 m
Tank capacity 2 l
Pump unit (L x W x H) 244 × 174 × 144 mm
Float switch (L x W x H) 82 x 39 x 39 mm
Switch points float switch Alarm: max. 53 | Start: 40 ± 2 | Stop: 20 ± 2
Alarm switch max. 230V, 8A (ohmix load) | NO normally open | NC normally closed
Pressure, suction hose 6 x 1,5 mm

This compact unit with integrated float is intended for use with units that are only equipped with a condensate collection tray, such as: air conditioning convectors, air conditioning cabinets, built-in units and water collection consoles. During operation, it must be ensured that no liquid runs via the pump!

Contact us

Your questions, our solutions: We are happy to help!

Working togehter to find the right product for your application.
Nach oben scrollen